When calculating the
fire resistance rating of glue laminated timber elements, it assumed that
charring of exposed surfaces of the Glulam member occurs at a uniform
rate, in the case of NZ Radiata Pine, it is taken as 0.65mm per minute.
When exposed to heat of a fire, timber undergoes a thermal breakdown (pyrolysis)
into combustible gases, and a layer of charcoal forms on the burning surface.
The Thermal Resistance
of softwood laminated flooring is rated at Rt = 0.81 m2°C/W (for 65mm
thickness). Insulation coverings will make a difference to the thermal
rating of the final product application. The New Zealand Standard 4214:1977
will assist further with calculations to include insulation coverings.
|
Flooring
Thickness
|
52mm
|
65mm
|
90mm
|
115mm
|
135mm
|
| Fire Rating |
½ hour |
1 hour |
1¼ hour |
1½ hour |
2 hours |
|